Application code | E+
|
Type version | mk3
|
Lamp type | TL5
|
Number of lamps | 3
piece/unit
|
Number of products on MCB (16 A type B) (nom.) | 16
|
Automatic restart | Yes
|
Input Voltage | 195-240
V
|
Input frequency | 50 to 60
Hz
|
Operating frequency (max.) | 110
kHz
|
Operating frequency (min.) | 45
kHz
|
Ignition method | Warm Start
|
Crest factor (max.) | 1.7
|
Power factor 100% load (nom.) | 0.95
|
Ignition time (max.) | 1
s
|
Mains voltage performance (AC) | -8%-+6%
|
Mains voltage safety (AC) | -10%-+10%
|
Earth leakage current (max.) | 0.5
mA
|
Inrush current width | 0.26
ms
|
Standby power consumption (max.) | 0.25
W
|
Ballast factor (nom.) | 1.0
|
Inrush current peak (max.) | 31
A
|
Efficiency at full load [%] | 90.54
%
|
Connector type input terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Cable capacity output wires mutual (max.) | 200
pF
|
Connector type output terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Connector type control input terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Wire strip length | 8.0-9.0
mm
|
Dual fixture master/slave | Yes
[ Master/Slave operation possible] |
Control input terminal cross section | 0.50-1.00
mm²
|
Input terminal cross section | 0.50-1.00
mm²
|
Output terminal cross section | 0.50-1.00
mm²
|
Auto-insert (ALF/ADS) wire cross section | 0.75
mm²
|
Cable capacity output wires to earth (max.) | 200
pF
|
Rated ballast-lamp power | 14/24 W
|
Rated lamp power on TL-D | 18
W
|
System power on TL-D | 57.6
W
|
Lamp power on TL-D | 17
W
|
Power loss on TL-D | 6.6
W
|
Rated lamp power on PL-L | 18/24
W
|
System power on PL-L | 50.3/75.2
W
|
Lamp power on PL-L | 15/22.9
W
|
Power loss on PL-L | 5.3/6.5
W
|
Rated lamp power on TL5 | 14/24
W
|
System power on TL5 | 49.1/77.2
W
|
Lamp power on TL5 | 15/23.3
W
|
Power loss on TL5 | 4.1/7.3
W
|
Rated lamp power on TL5 ECO | 13/20
W
|
System power on TL5 ECO | 43.5/66.5
W
|
Lamp Power on TL5 ECO | 13.6/20.1
W
|
Rated lamp power on TL-D ECO | 16
W
|
System power on TL-D ECO | 46.5
W
|
Power loss on TL-D ECO | 5.4
W
|
Lamp power on TL-D ECO | 13.7
W
|
Power loss on TL5 ECO | 2.7/6.2
W
|
T-ambient (max.) | 50
°C
|
T-ambient (min.) | -25
°C
|
T storage (max.) | 80
°C
|
T storage (min.) | -40
°C
|
T case lifetime (max.) | 75
°C
|
T-Case maximum (max.) | 75
°C
|
Stable lamp operation temperature | 15°C
|
T-Ignition (max.) | 50
°C
|
T-Ignition (min.) | -25
°C
|
Control interface | TD
|
Regulating level power | 1%-100%
|
Control input protection | Yes (Basic insulation)
|
Housing | L 360x39x22
|
Battery voltage lamp ignition | 198-254
V
|
Battery voltage lamp operation | 176-254
|
Energy efficiency index | A1 BAT
|
||
IP classification | IP 20
[ Ingress Protection 20] |
||
EMI 9 kHz ... 30 MHz | EN55015
|
||
EMI 30 MHz ... 1,000 MHz | EN 55022 Class B
|
||
Safety standard | IEC 61347-2-3
|
||
Performance standard | IEC 60929
|
||
Quality standard | ISO 9000:2000
|
||
Environmental standard | ISO 14001
|
||
Harmonic current emission standard | IEC 61000-3-2
|
||
EMC immunity standard | IEC 61547
|
||
Vibration standard | IEC68-2-6 F c
|
||
Bumps standard | IEC 68-2-29 Eb
|
||
Humidity standard | EN 61347-2-3 clause 11
|
||
Approval marks | CE marking
|
ENEC certificate
|
VDE-EMV certificate
|
Temperature marking | Yes
|
||
Emergency standard | IEC 60598-2-22
|
||
Humming and noise level | Inaudible
|
Full product code | 871829115676500
|
Order product name | HF-Ri TD 3 14/24 TL5 E+ 195-240V
|
EAN/UPC – product | 8718291156765
|
Order code | 913700679066
|
SAP numerator – quantity per pack | 1
|
Local code description | REATOR ELETRONICO FLUOR HF-Ri TD314E+
|
Numerator – packs per outer box | 10
|
SAP material | 913700679066
|
Net Weight (Piece) | 0.377
kg
|